16~18V Protection type : Shut down o/p voltage, re-power on to recover
Overtemperature
80° C ±5° C (12V), 85° C ±5° C (24V,48V) (TSW1: detect on heatsink of power transistor) 85° C ±5° C (12V), 75° C ±5° C (24V,48V) (TSW2 : detect on heatsink of o/p diode) Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
Short Circuit
YES, protected by internal circuit
Reverse Polarity
YES, protected by internal circuit
Function
Remote Control
Open: Normal work Short: Stop Charging
Batterbanks
2 banks (A & B)
Fastcharge
2 / 3 / 8 stage selectable
Charger Ok
Relay contact rating(max.): 30V/1A resistive ; "Short" when the unit is working properly, "Open"when the unit is failure or the protection function is activating
Output Ok
Relay contact rating(max.): 30V/1A resistive ; "Short" when the battery is full, "Open" when the battery is still charging
Temperature Compensation
By NTC, compensate both banks at the same time
Environment
Workingtemp.
-20 ~ +60° C (Refer to "Derating Curve")
Workinghumidity
20 ~ 90% RH non-condensing
Storage Temp., Humidity
-40 ~ +85° C, 10 ~ 95% RH
Temp. Coefficient
±0.05%/° C(0~50° C)
Vibration
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes